Electric two-way control valve installation and troubleshooting
1. Electric two-way control valve installation and use precautions Newly designed and installed control system, in order to ensure the electric thermostat valve can work properly and make the system safe operation, the new valve before installation, you should first check the nameplate tag on the valve Is it consistent with the design requirements? The following items should also be debugged. Basic error limit; full stroke deviation; backlash; dead zone; leakage (in demanding occasions). If it is the original system of electric two-way control valve overhaul, in addition to the above-mentioned verification, but also the old valve should be stuffing box and connections and other parts of a tightness check. Electric two-way valve in the field of use, often not because of the quality of the control valve itself caused, but the installation of electric two-way valve caused by improper use, such as the installation of the environment, the installation location and direction of improper or pipeline is not Cleaning and other reasons. Therefore, the electric two-way control valve should pay attention to the following aspects when installing and using: (1) The electric two-way control valve belongs to the field instrument, the ambient temperature should be -25 ~ 60 ℃ and the relative humidity ≤95%. If it is installed in open air or high temperature occasions, should take waterproof, cooling measures. In the place with the source to stay away from the vibration source or increase the anti-vibration measures. (2) The electric two-way control valve should be installed vertically. In special circumstances, it can be tilted. For example, when the tilt angle is very big or the valve itself is too heavy, support for the valve should be increased. (3) Installation of electric two-way control valve pipe generally not from the ground or the floor is too high, the pipe height is greater than 2m should be set as the platform, in order to facilitate the operation of the hand wheel and easy maintenance. (4) electric two-way control valve should be installed before the pipeline cleaning, remove dirt and welding slag. After installation, in order to ensure that no impurities remain in the valve body, the valve should also be cleaned again, that is, the medium should be opened so that all valves open to prevent impurities stuck. After using the hand wheel mechanism should be restored to the original neutral position. (5) In order to make the electric two-way control valve in case of failure or maintenance of the production process can continue, electric two-way control valve should be bypassed. At the same time should also pay special attention to the installation position of the electric two-way control valve meets the requirements of the process. (6) The installation of the electric part of the electric two-way regulating valve shall be based on the construction requirements of the relevant electrical equipment. In the case of explosion-proof products, they should be installed in accordance with the "Installation Specification for Electrical Equipment in Explosion Hazardous Locations". Such as the scene wire SBH or other six-core or eight core, outer diameter of about Φ11.3mm rubber mounting cable. In the use of maintenance, in the explosive place is strictly prohibited open cover repair and blasting face pry. At the same time do not knock in the disassembly or scratch explosion-proof surface, after repair to restore the original flameproof state. (7) After the actuator reducer repair should pay attention to refueling lubrication, low-speed motor generally do not demolition and refueling. Assembly should also check the valve position and valve position opening instructions are consistent. 2. Electric two-way control valve parts and the common causes of failure Wo-electric two-way control valve performance will have a direct impact on the quality of the entire regulatory system. As the regulating valve in the field is in direct contact with the medium to be adjusted, the working environment is very poor, so easy to produce a variety of failures. In the production process, in addition to ruled out these failures at any time, but also must be regular maintenance and regular maintenance. Especially for the use of particularly harsh environment control valve, but should pay attention to maintenance and regular maintenance. Different forms of control valve, the failure and its causes are not the same. Now in the valve in the production of straight stroke electric two-way control valve, for example, describes the general failure of electric control valve and maintenance methods. 2.1 Servo amplifier Servo amplifier normal working condition: (1) no input signal, there should be no output voltage. (2) Open loop dead zone current ≤160μA (Ⅱ type is 100μA). (3) When the input signal is> 240μA (type 150μA), the output load voltage is 205 ~ 220VAC. (4) The output voltage is basically symmetrical. If the servo amplifier is not working properly, each part may have the following situations: (1) Front magnetic amplifier ①When there is no signal input, the output of the dual-shot magnetic amplifier can be adjusted to zero through the potentiometer W101. Can not be zero may be: A, W101 desoldering transformer or damaged. B, resistance R110, R111 and electrolytic capacitors C101, C102 Weld or desoldering. C, diodes D105 ~ D108 Weld or damaged. D, the offset current is not normal. E, AC winding asymmetry. ② There is input signal, but no output or output asymmetry may be: A, transformer B301 for the AC winding current secondary voltage asymmetry. B, the resistance of the resistors R110 and R111 has changed, the electrolytic capacitors C110, C111 damaged. C, AC excitation winding short circuit. D, diode D105 ~ D108 in some of the tube damage or Weld. Trigger input, the trigger on one side of the oscilloscope screen should have a pulse signal, change the polarity of the input signal, then the other side of the trigger pulse signal. The trigger pulse number and amplitude of two groups should be basically the same. Otherwise there are the following situations. ①no input signal (front magnetic amplifier in normal working condition), the output trigger pulse may be: A, trigger pulse output side of the transistor damage, or c, e very Weld. B, resistance R204, R205, R208, R209 resistance has changed. ② input signal, the output without trigger pulse, may be: A, no output pulse side of the transistor, single junction tube damage. B, no output pulse side of the pulse transformer primary or secondary open circuit or short circuit. C, no output pulse side of the diode (D207 or D208) short circuit. The output trigger pulse is not normal There are several phenomena: A, no signal when the two sets of triggers have a pulse output, plus the signal are normal, may be electrolytic capacitors C202 or C203 Weld. B, the beginning of the trigger output on both sides are normal, after a period of work, the output pulse gradually disappear, monosomy tube may have problems. C, the output appears positive and negative pulses, it may be diode D207, D208 was punctured or Weld. (3) After the above inspection and maintenance, the servo amplifier should work normally without any fault in the control loop. Otherwise, there are the following two cases: ①Without input signal, the output voltage (voltage approaching 220VAC) may be: A, thyristor SCR1, SCR2 damage. B, the capacitor C301, C302 is breakdown. ② When there is input signal, there is no output signal or the output voltage is low, it may be: A, D301 ~ D308 diodes have breakdown. B, thyristor SCR1, SCR2 damage. 2.2 electric two-way control valve When the input 4 ~ 20mA signal, the control valve stem in the rated stroke with the signal changes up and down freely. If it can not operate normally, it may have the following faults: ①The operating handwheel feels abnormal. A. It feels too light. It may be that the handwheel latch is off or broken. B, feeling too heavy or spinning. There are foreign objects in the reducer jam; spool and bushing or seat stuck; serious bending stem. ② input 4 ~ 20mA signal, the control valve does not move. A, the system wiring is wrong. B, the motor phase-split capacitor CD is damaged. C, motor wiring open. D, the spool off or stem breakage (at this time the actuator has an action) ③ input 4 ~ 20mA signal, regulating valve can not go through the rated travel. A, differential transformer position is not adjusted. B, some of the diodes D701 ~ D712 are damaged. C, transistor BG701 damaged. (4) other failures in the field. ①valve turbulence, tweets. A, the sensitivity is too high, the implementing agencies have oscillations. B, the fluid pressure changes too much, the actuator thrust is not enough. C, the choice of control valve, the valve often work in a small opening. D, the direction of flow of medium and valve closing direction. E, near the impact of other sources, support instability. F, spool and bushing wear serious. ② electric two-way valve slow action. A, the media is too viscous, clogging or coking phenomenon. B, filler aging, packing pressed too tight. ③ large amount of leakage. A, spool or valve seat is corroded and worn. B, the seat is loose or the thread is corroded. C, seat, spool foreign body. D, the valve starting point (electric open) or the end (electric closed) is not adjusted. ④ packing and the upper and lower bonnet junction leakage. A, packing gland did not compress. B, PTFE filler aging deterioration. C, stem damage. D, tighten the nut loose. E, seal damage.