Design and Application of ANAPF Active Filter in Jiangyin Textile Enterprise

This paper introduces the working principle, scheme, technical parameters and product characteristics of ANAPF active filter device.

Ankerui Electric Co., Ltd.



Abstract: This paper introduces the working principle, scheme, technical parameters and product characteristics of the ANAPF active filter device. Combined with the application case in a low-voltage power distribution system of a well-known textile enterprise in Jiangsu, the active filter device is described in the low-voltage power distribution system. It plays a vital role in improving the quality of power supply and harmonics.



Keywords: low-voltage distribution system active filter device working principle scheme characteristics application harmonic


introduction
With the increasing use of power electronic converters, electric energy has been more fully utilized. However, the wide application of nonlinear power device equipment produces a large number of distorted current harmonics. The flow of distorted current in the power grid leads to harmonic voltage; harmonic pollution increasingly threatens the safety, stability and economic operation of the power system. It has a significant impact on the linear load of the same network and other users. Harmonics have been combined with electromagnetic interference and power factor reduction as the three major public hazards of the power system. Therefore, understanding the principle of harmonic generation and studying the elimination of higher harmonics in power supply and distribution systems have a very positive significance for improving the quality of power supply and ensuring the safe and economic operation of power systems. Harmonic measurement is an important branch of the harmonic problem, and it has an important guiding role in suppressing harmonics and solving the problems caused by harmonics. Therefore, the measurement and analysis of harmonics is an important task in power system analysis and control, and it is an important prerequisite for relay protection and fault measurement.


1. Working principle The ANAPF series active power filter device is connected in parallel to the low-voltage power distribution system with harmonic load, which can track and compensate the dynamically changing harmonic current in real time. The principle is as follows: ANAPF series active power filter collects the harmonic current of the system through CT, and quickly calculates and extracts the content of each harmonic current through the controller, generates harmonic current command, generates harmonic current series through power execution device. The compensation currents are equal in opposite directions and injected into the power system to cancel the harmonic current generated by the nonlinear load.



China Hardware Business Network


ANAPF active power filter schematic




2. APF product technical parameters

ANAPF active power filter technical parameters

Wiring

Three-phase three-wire or three-phase four-wire

Access voltage

3×380±10%

Access frequency

50Hz±2%

Transient response time

100μs

On-off level

10kHz-20kHz

Function setting

Only compensate for harmonics, only compensate for reactive power, compensate for harmonics and compensate for reactive power

Harmonic compensation times

2-31 times

Type of protection

DC overvoltage protection, IGBT overcurrent protection, device over temperature protection

cooling method

Forced air cooling

noise

<65dB (in the cabinet and operating in rated state)

Working temperature

-10°C~+45°C (the ambient temperature exceeds the working temperature range for derating)

Working environment humidity

<85% RH does not condense

Installation occasion

Indoor installation

Altitude

≤1000M (higher altitude needs derating)

In and out line

According to customer requirements

Protection level

IP30

Intelligent communication interface

RS485/MODBUS-RTU

Remote monitoring

Optional

Installation method

Cabinet type

Wall-mounted

Drawer type

Compensation current size (A)

50, 100, 150

200, 250, 300

30, 50

30, 50

Cabinet color

RAL7035

Among the three installation methods of the active filter device, the wall-mounted and drawer-type are economical solutions of the vertical cabinet type, which greatly saves the cost for the user. A single module with a maximum capacity of 50A can be used alone. Multiple 50A modules can also be used to form a large current compensation device.



3. Scheme design In response to the harmonics of a well-known textile enterprise project in Jiangsu, the relevant technical personnel conducted detailed measurements on the outlet side of the 1# transformer with a capacity of 2500KVA. The main harmonic frequency is 5, 7 and 11 times is a typical 6n ± 1 harmonic.
Measurement diagram: (black circle is the measuring point)



China Hardware Business Network



According to the measured power quality analysis and specific measurement data, combined with the harmonic calculation formula (1) (2) (3), the harmonic current can be estimated.

China Hardware Business Network …………………………………………………(1)

China Hardware Business Network ………………………………………(2)

China Hardware Business Network ....................................(3)

( China Hardware Business Network Total harmonic current China Hardware Business Network Fundamental current RMS China Hardware Business Network Full wave current RMS China Hardware Business Network Total harmonic current distortion rate)

Calculated by the above formula, the harmonic current of the 1# transformer outlet cabinet can be calculated as shown in the table.

Measuring point

Current Irms(A)

THDi

Harmonic current In(A)

1# transformer outlet cabinet

3065.1

11.96%

366.59

Harmonic control considers that the harmonics should be cleaned. The harmonic filter should be larger than the actual current when selecting the harmonic filter. It is determined that the active filter devices of the 2# ANAPF200-380/BGL are concentrated in the outlet of the 1# transformer. Governance.



4. Product design
4.1 Electrical Design The ANAPF200-380/BGL active filter unit consists of four 50A drawer onboard modules. The main incoming line is equipped with a molded case circuit breaker. The principle is as follows:



China Hardware Business Network



4.1.1 Design of the onboard module of the drawer China Hardware Business Network
Dimensions 485 × 610 × 275 (width * depth * height)
Rated current: 50A
Rated voltage: AC380V
Wiring method: three-phase four-wire incoming line mode: after entering and leaving the rated frequency: 50Hz
Module housing color: RAL9004
Protection level: IP20
Quality: 50KG
4.2 Cabinet structure design as shown below, the cabinet size is 1000*2200*800 (width and depth), the cabinet color is RAL7035, GGD cabinet type, galvanized sheet material, the installation method is to match the power distribution cabinet, the cabinet design In line with the principle of coordination with other low-voltage cabinets.



China Hardware Business Network










5. Product Features ● Modular design, low cost, improved performance, small size, convenient installation, convenient for later maintenance and expansion;
● DSP+FPGA full digital control mode, with extremely fast response time, advanced main circuit topology and control algorithm, higher precision and more stable operation;
●One machine can multiply, it can compensate harmonics, and it can complement the reactive power. It can compensate for the full compensation of 2-31 harmonics or specify specific harmonics.
● It has perfect bridge arm over-current protection, DC over-voltage protection and device over-temperature protection function;
● Each module adopts a color touch screen to realize parameter setting and control, which is convenient to use and easy to operate and maintain;
● Filtering device is installed at the output to reduce the influence of high frequency ripple on the power system;



6. Application case
6.1 Project Overview and Requirements A well-known textile enterprise in Jiangsu uses the load such as inverter to generate a large number of harmonics, which causes the capacitor of the capacitor cabinet to be damaged, thus reducing the actual power factor. Since the power factor does not meet the requirements of the national standard of 0.9, the power supply The department took economic penalties for the company, which seriously affected the normal operation of the company.
6.2 Harmonic control effect



China Hardware Business NetworkChina Hardware Business Network

Figure 1 Current waveform before putting into use Figure 2 Current spectrum before putting into use From Figure 1 and Figure 2, it can be seen that the current waveform is the waveform of the typical three-phase rectifier bridge nonlinear load, and the current harmonic of the inverter is reflected in Figure 2. The total distortion rate is 11.96%, the 5th harmonic current is 331.6 A, and the 7th harmonic current is 89.8A. In addition to this, there are 11 times, 12 current harmonics, and the other harmonics are negligible.



China Hardware Business NetworkChina Hardware Business Network

Figure 3 Current waveform after being put into use Figure 4 Current spectrum after being put into use
After inputting the active power filter, the waveform and harmonic content of the inverter power supply have changed. From Figure 3, it can be seen that the current waveform has become close to a sine wave. Figure 4 shows the total input current of the inverter. The distortion rate was reduced to 4.8%, the 5th harmonic current was changed from the original 331.6A to 92.2A, and the 7th harmonic current was changed from the original 89.8A to 13.8A. The other harmonics were also eliminated. The application of active power filters has brought new highlights to enterprises to eliminate grid pollution, save energy and reduce consumption.


7. Conclusion The active filter cabinet selected for this project is the latest modular design scheme, which is small in size, low in cost, convenient in installation, convenient for future maintenance and expansion; easy to use and easy to operate; active filter device saves user investment cost. The construction period has been shortened, and an efficient compensation device for the harmonic control project of the low-voltage distribution network has been provided, which has good application value and application prospect.


[References]
[1] Ankerui Power Quality Monitoring and Governance Selection Manual. 2015.08 version [2] Ankerui Electric Co., Ltd. Product Manual.2013.01.



About the Author

Yang Junjun, female, undergraduate. Position: Now working at Ankelui Electric Co., Ltd. Tel, mobile, QQ
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

Our aluminum alloy Emergency Restoration Tower has different structures. The LTQ110S type is designed with single-leg structure, while the rest types possess the portal-framed structure. Moreover, the 220kV portal-framed tower can also assemble the 110kV portal-framed type or 110kV single-leg type.

And our Aluminum Alloy Crossing Structure is fitted with the 04171 crossing structure backward installation lifter that needs to be purchased additionally.


Tower

Emergency Restoration Tower And Crossing Structure

Emergency Restoration Tower, Aluminum Alloy Crossing Structure

NINGBO MARSHINE POWER TECHNOLOGY CO., LTD. , https://www.marshine-power.com